![background image](http://html1.mh-extra.com/html/daikin/fhq100buv1b-x-2/fhq100buv1b-x-2_service-manual_2459261022.webp)
SiBE28-804
Specifications
Specifications
11
Notes:
1. Nominal cooling capacities are based on:
Indoor temperature: 27.0°C DB/19.0°C WB
Outdoor temperature: 35.0°C DB
Equivalent refrigerant piping: 7.5 m
Level difference: 0 m
2. Nominal heating capacities are based on:
Indoor temperature: 20°C DB
Outdoor temperature: 7.0°C DB/6.0° C WB
Equivalent refrigerant piping: 7.5 m
Level difference: 0 m
Piping
connections
Liquid quantity
1
Liquid type
Flare connection
Liquid diameter (OD)
9.52 mm
Gas quantity
1
Gas type
Flare connection
Gas diameter (OD)
15.9 mm
Drain quantity
3
Drain type
Hole
Drain diameter (OD)
26.0 mm
Piping length min.
5 m
Piping length max.
50 m
75 m
Piping length equivalent
70 m
95 m
Piping length chargeless
30 m
Additional refrigerant charge
See installation manual
4PW40417-1
See installation manual 4PW34874-1
Installation height difference max.
30.0 m
Max. intern unit level difference
0.50 m
Heat insulation
Both liquid and gas pipes
Defrost method
Pressure equalising
Defrost control
Sensor for outdoor heat exchanger temperature
Capacity control method
Inverter controlled
Safety devices
High pressure switch
Fan motor thermal protector
Fuse
Standard
accessories
Item
Tie-wraps
Quantity
2
Standard
accessories
Item
Installation manual
Quantity
1
Specification
RZQ71C7V1B
RZQ100C7V1B
RZQ125C7V1B
RZQ140C7V1B
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...