Field Settings
SiBE28-804
110
Test Operation
2.13 Setting for Low Humidity Application
Purpose
Can be set when using the RZQ units for year round cooling in low humidity applications such
as computerrooms (EDP rooms), technical rooms, etc...to increase the capacity of the unit.
Definition of Low
Humidity Area
Caution
When using the "LH settings" outside the "Low Humidity Area" there is an increased risk of ice
accumulation on the indoor coil or water blowing out from the indoor unit.
Relative
Humidity
(%)
Setting is only allowed in this area
Indoor side temperature DB (˚C)