background image

DELTA 18-21-24

Indoor Units

Outdoor Units

DELTA 18

GC 18

DELTA 21

GC 22

DELTA 24

OU7-24
OU7-24Z

Service Manual

SM DELTA 1-E.0 GB

JUNE – 2010

REFRIGERANT

R410A

HEAT PUMP

COOLING ONLY

Summary of Contents for DELTA 18

Page 1: ...DELTA 18 21 24 Indoor Units Outdoor Units DELTA 18 GC 18 DELTA 21 GC 22 DELTA 24 OU7 24 OU7 24Z Service Manual SM DELTA 1 E 0 GB JUNE 2010 REFRIGERANT R410A HEAT PUMP COOLING ONLY...

Page 2: ...anged pages are Original 0 JUNE 2010 Total number of pages in this publication is 93 consisting of the following Page No Revision No Page No Revision No Page No Revision No Title 0 A 0 i 0 1 1 1 3 0 2...

Page 3: ...1 5 PERFORMANCE DATA PRESSURE CURVES 5 1 6 SOUND LEVEL CHARACTERISTICS 6 1 7 ELECTRICAL DATA 7 1 8 WIRING DIAGRAMS 8 1 9 ELECTRICAL CONNECTIONS 9 1 10 REFRIGERATION DIAGRAMS 10 1 11 TUBING CONNECTION...

Page 4: ...ration sound level Bended Indoor coil with treated aluminum fins and coating for improved efficiency High COP Easy access to the interconnecting tubing and wiring connections Refrigerant pipes can be...

Page 5: ...ial fan Outdoor coil with hydrophilic louver fins for RC units Compressor mounted in a soundproofed compartment Outlet air fan grill Service valves flare type connection Interconnecting wiring termina...

Page 6: ...RC R410A GC 22 ST RC R410A GC 24 ST RC R410A OU7 24 R410A OU7 24Z R410A The above table lists outdoor units and DELTAindoor units which can be matched together In addition the listed outdoor units ca...

Page 7: ...Units per pallet units 16 Stacking height units 8 OUTDOOR Refrigerant control Capillary tube Compressor type model Rotary TOSHIBA PA200X2CS 4KU1 Fan type quantity Propeller direct x 1 Fan speeds H L R...

Page 8: ...per pallet units 16 Stacking height units 8 OUTDOOR Refrigerant control Capillary tube Compressor type model Rotary TOSHIBA PA240X2CS 4KU1 Fan type quantity Propeller direct x 1 Fan speeds H L RPM 815...

Page 9: ...t kg 18 Units per pallet units 16 Stacking height units 8 OUTDOOR Refrigerant control Capillary tube Compressor type model Rotary Fan type quantity AXIAL 1 Fan speeds H L RPM 850 720 Air flow H L m3 h...

Page 10: ...25x360x280 Packaged weight kg 18 Units per pallet units 16 Stacking height units 8 OUTDOOR Refrigerant control Capillary tube Compressor type model Rotary Fan type quantity AXIAL 1 Fan speeds H L RPM...

Page 11: ...18 Units per pallet units 16 Stacking height units 8 OUTDOOR Refrigerant control Capillary tube Compressor type model Rotary Fan type quantity AXIAL 1 Fan speeds H L RPM 850 720 Air flow H L m3 hr 310...

Page 12: ...ling Indoor 27o C DB 19o C WB Outdoor 35 o C DB Heating Indoor 20o C DB Outdoor 7o C DB 6o C WB 3 1 Operating Limits 3 1 1 R410A Indoor Outdoor Cooling Upper limit 32o C DB 23o C WB 46o C DB Lower lim...

Page 13: ...4 1 OUTLINE DIMENSIONS SM DELTA 1 E 0 GB 4 OUTLINE DIMENSIONS 4 1 Indoor Unit DELTA 18 21 24 4 2 Outdoor Unit GC 18 22...

Page 14: ...4 2 OUTLINE DIMENSIONS SM DELTA 1 E 0 GB 4 3 Outdoor Unit OU7 24 OU7 24Z...

Page 15: ...I 1 38 1 39 1 40 1 41 1 42 30 TC 4 83 5 26 5 68 5 88 6 05 SC 3 58 3 80 4 04 4 16 4 24 PI 1 49 1 51 1 52 1 54 1 55 35 TC 4 47 4 85 5 35 5 62 5 88 SC 3 40 3 65 3 95 4 06 4 14 PI 1 61 1 63 1 66 1 67 1 68...

Page 16: ...37 1 73 6 21 1 84 20 6 89 1 65 6 72 1 79 6 53 1 93 the above chart includes the weighted deicing in euence LEGEND TH Total Heating Capacity kW PI Power Input kW WB Wet Bulb Temp o C DB Dry Bulb Temp o...

Page 17: ...0 11 5 12 0 15 20 25 30 35 40 46 Outdoor Temp DB o C Suction Pressure Bar g 15 21 WB DB C 17 24 WB DB C 19 27 WB DB C 21 29 WB DB C 23 32 WB DB C Discharge Pressure VS Outdoor Temp 10 12 14 16 18 20...

Page 18: ...or Temp 3 0 4 0 5 0 6 0 7 0 8 0 9 0 10 0 11 0 12 0 10 5 0 5 10 15 20 Outdoor Temp WB o C Suction Pressure Bar g 15 DB C 20 DB C 25 DB C Discharge Pressure VS Outdoor Temp 14 16 18 20 22 24 26 28 30 32...

Page 19: ...1 4 75 4 89 4 98 PI 1 71 1 72 1 73 1 74 1 75 30 TC 5 59 6 09 6 58 6 81 7 02 SC 4 11 4 37 4 65 4 78 4 87 PI 1 84 1 87 1 88 1 90 1 91 35 TC 5 18 5 62 6 20 6 51 6 82 SC 3 91 4 19 4 54 4 67 4 76 PI 1 98 2...

Page 20: ...7 2 06 7 67 2 22 7 48 2 36 20 8 29 2 12 8 09 2 30 7 87 2 48 the above chart includes the weighted deicing in euence LEGEND TH Total Heating Capacity kW PI Power Input kW WB Wet Bulb Temp o C DB Dry Bu...

Page 21: ...5 7 PERFORMANCE DATA PRESSURE CURVES SM DELTA 1 E 0 GB 5 6 Pressure Curves 5 6 1 Cooling...

Page 22: ...5 8 PERFORMANCE DATA PRESSURE CURVES SM DELTA 1 E 0 GB 5 6 2 Heating...

Page 23: ...3 SC 4 58 4 86 5 13 5 28 5 37 PI 1 86 1 88 1 89 1 90 1 91 30 TC 6 11 6 65 7 19 7 44 7 66 SC 4 44 4 72 5 02 5 16 5 26 PI 2 01 2 04 2 06 2 07 2 09 35 TC 5 66 6 14 6 77 7 11 7 45 SC 4 22 4 52 4 90 5 04 5...

Page 24: ...2 8 35 2 61 8 14 2 77 20 9 03 2 49 8 81 2 70 8 57 2 91 the above chart includes the weighted deicing in euence LEGEND TH Total Heating Capacity kW PI Power Input kW WB Wet Bulb Temp o C DB Dry Bulb Te...

Page 25: ...20 25 30 35 40 46 Outdoor Temp DB o C Suction Pressure Bar g 21 15 DB WB C 24 17 DB WB C 27 19 DB WB C 29 21 DB WB C 32 23 DB WB C Discharge Pressure VS Outdoor Temp 14 16 18 20 22 24 26 28 30 32 34...

Page 26: ...VS Outdoor Temp 3 4 5 6 7 8 9 10 11 12 10 5 0 5 10 15 20 Outdoor Temp WB o C Suction Pressure Bar g 15 DB C 20 DB C 25 DB C Discharge Pressure VS Outdoor Temp 14 16 18 20 22 24 26 28 30 32 34 36 38 40...

Page 27: ...ic Unit Wall BAND CENTER FREQUENCIES Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 002 MICRO BAR BAND CENTER FRE...

Page 28: ...dB re 0 002 MICRO BAR BAND CENTER FREQUENCIES Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 002 MICRO BAR BAND...

Page 29: ...4 Heating BAND CENTER FREQUENCIES Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 002 MICRO BAR BAND CENTER FREQUE...

Page 30: ...er A 15 20 3 10 Power Supply Wiring No X Cross Section mm2 3 1 5 mm2 3 2 5 mm2 5 1 5 mm2 Interconnecting Cable RC Model No X Cross Section mm2 5 1 5 mm2 2 0 5 mm2 OCT senser 6 1 5 mm2 2 0 5 mm2 OCT se...

Page 31: ...8 1 WIRING DIAGRAMS SM DELTA 1 E 0 GB 8 WIRING DIAGRAMS 8 1 Indoor Unit DELTA 18 21 24...

Page 32: ...8 2 WIRING DIAGRAMS SM DELTA 1 E 0 GB 8 2 Outdoor Unit GC 18 1PH R410A...

Page 33: ...8 3 WIRING DIAGRAMS SM DELTA 1 E 0 GB 8 3 Outdoor Unit GC 24 1PH R410A...

Page 34: ...8 4 WIRING DIAGRAMS SM DELTA 1 E 0 GB 8 4 Outdoor Unit OU7 24 1PH R410A...

Page 35: ...8 5 WIRING DIAGRAMS SM DELTA 1 E 0 GB 8 5 Outdoor Unit OU7 24 3PH R410A...

Page 36: ...8 6 WIRING DIAGRAMS SM DELTA 1 E 0 GB 8 6 Outdoor Unit OU7 24Z R410A...

Page 37: ...1 1PH 9 2 DELTA 24 1PH power supply to Outdoor unit INDOOR UNIT POWER SUPPLY 1PH 220 240V 50Hz CIRCULIT BREAKER NOT SUPPLIED CONNECTED ONLY HEAT PUMP UNIT OUTDOOR UNIT INDOOR UNIT POWER SUPPLY 1PH 220...

Page 38: ...Service Outdoor coil Sensor Capillary tube Strainer Check valve OUTDOOR UNIT valve Reverse tube Capillary Compressor Outdoor coil Sensor tube Capillary Reverse Strainer valve Compressor tube Capillar...

Page 39: ...10 2 REFRIGERATION DIAGRAMS Service Manual ALPHA 10 1 2 DELTA 24 OU7 24 R410A...

Page 40: ...10 3 REFRIGERATION DIAGRAMS SM DELTA 1 E 0 GB 10 1 3 DELTA 24 OU7 24Z R410A...

Page 41: ...ON DIAGRAMS Service Manual ALPHA 10 2 Cooling Only Models 10 2 1 DELTA 18 21 24 R410A Outdoor coil Strainer Capillary tube Compressor Service port OUTDOOR UNIT connection Valves Flared Indoor coil Sen...

Page 42: ...3 1 Valve Protection Cap end 2 Refrigerant Valve Port use Allen wrench to open close 3 Valve Protection Cap 4 Refrigerant Valve 5 Service Port Cap 6 Flare Nut 7 Unit Back Side 8 Copper Tube When the o...

Page 43: ...is designed for service applications and is common to the following groups of air conditioners ST RC group Cooling only cooling and heating by heat pump SH group Cooling and heating by heat pump and s...

Page 44: ...High Water Level LEVEL4 Over ow Level Max Maximum Min Minimum min Minute time NA Not Applicable OCP Outdoor Condensation Pump OCT Outdoor Coil Temperature RT3 sensor OF OFAN Outdoor Fan OPER Operate P...

Page 45: ...B Controller 12 3 1 LED Display DELTA STAND BY OPER INDICATOR SIGNAL RECEIVER MODE RESET BUTTON FILTER LED TIMER LED 5HVHW EXWWRQ 0RGH EXWWRQ 7R URRP VHQVRU 7R LQGRRU VHQVRU X HU 7R GLVSOD 7R VWHS PRW...

Page 46: ...between IFAN speed change in H M L Mode is 1 sec IFAN speed in Heat Cool Autofan Mode is determined according to the following table T IFAN Speed T 2 HIGH 2 T 1 MED 1 T LOW where in Heat Mode T SPT RT...

Page 47: ...o c b Thermistor is shorted The thermistor reading is over 75o c c Thermistor Temp reading doesn t change irrelevant for RT1 i This test is performed only once after a unit is switched from OFF STBY t...

Page 48: ...e unit can continue the normal operation All protections related to that faulty thermistor will be disabled For example in case of any ICT fault the ICT high pressure protection in Heat Mode and ICT d...

Page 49: ...ution of RT is 1o c RT is activating COMP WVL if RT SPT and RT is stopping COMP WVL if RT SPT 3 Indoor Coil Temp is detected by ICT RT2 4 Outdoor Coil Temp is detected by OCT RT3 5 A WVL RC SH will wo...

Page 50: ...Off Control function Maintains room temp at desired level by comparing RT and SPT RT SPT oc 3 2 1 0 1 2 ON OFF ON OFF USER FAN SPEED ON OFF COMP WVL OFAN IFAN RV Note 1 IFAN is always running at High...

Page 51: ...de Cool Auto at cooling Temp Selected desired temperature Fan Auto Timer Any I Feel On or Off Control function Maintains room temp at desired level and controls the IFAN speed for optimal comfort RT S...

Page 52: ...switched ON In this case the IFAN will be started at low speed Notes 1 In SH or RC group if HE is set to OFF due to low ICT IFAN will be switched to LOW and will be turned OFF after 30 sec 2 An except...

Page 53: ...In SH or RC group HE operation is limited by the following graph Back up mode for SH group After COMP has been working for 5 minutes HE IFAN are activated even if the ICT is still below 35o c This sit...

Page 54: ...uto at heating Temp Selected desired temperature Fan HIGH MED LOW Timer Any I Feel On or Off Control function Maintains room temp at desired level by comparing RAT or RCT to SPT RT SPT o c 2 1 0 1 2 3...

Page 55: ...Mode Heat Auto at heating Temp Selected desired temperature Fan Auto Timer Any I Feel On or Off Control function Maintains room temp at desired level by controlling COMP IFAN and OFAN RT SPT oc 2 1 0...

Page 56: ...NTROL SYSTEM SM DELTA 1 E 0 GB 12 6 6 OFAN operation is controlled by the graph below when 1 RAT SPT 2o c AND 2 ICT 45o c AND 3 COMP is ON Otherwise OFAN runs together with COMP OCT o c 3 2 1 0 1 OFAN...

Page 57: ...eed The proper Auto Heat mode or Auto Cool will be started whenever the RT reaches SPT 1o c or SPT 1o c respectively For RC SH units Mode change between Auto Heat Auto Cool Modes is possible only afte...

Page 58: ...Any I Feel On or Off Control function Maintains room temp at desired level by selecting between cooling and heating modes RT SPT o c 3 2 1 0 1 2 3 ON OFF ON OFF H M L OFF L OFF ON OFF ON OFF COMP OFA...

Page 59: ...n of continuous COMP operation When Dry is OFF the COMP is forced ON for 6 min longer than the 3 min Min COMP On time after every 15 min of continuous COMP OFF time When Dry is changed from ON to OFF...

Page 60: ...for 10 min minimum Notes When J7 is closed connected OFAN cycling is cancelled and the set temperature for COMP OFAN cut out and cut in are changed COMP OFAN are forced OFF when ICT 6o c and are kept...

Page 61: ...R LED 52 55 61 66 L COMP is forced OFF OFAN is forced ON IFAN forced to LOW 68 OFAN follow operation of COMP COMP is forced OFF OFAN is forced ON For all models except WAX P2000 For WAX P2000 models N...

Page 62: ...V operation Scope This new deicer is designed to operate at extreme temp conditions The deicing cycle could be triggered from 1 OCT temp and time between two consecutive deicing cycles 2 Detection of...

Page 63: ...ed BLINK ON OPER LED Notes At the rst COMP activation after SB or OFF if OCT 0o c then DI 10 min else DI 40 min In the following Deicing cycles the time interval between two Deicing cycles activation...

Page 64: ...f COMP is forced OFF For all models except WAX For WAX model ON BLINK OPER LED Notes IFAN HE1 and HE2 will be activated according to the relevant Heating Mode Sect In case of any malfunction in the re...

Page 65: ...is blinked to indicate the situation The LED keeps blinking until the timer settings can be reloaded from a R C message Note If all timers are inactive the system will not be forced OFF after the powe...

Page 66: ...ng to the following table Forced operation mode Pre set Temp for WMF WMN WNG models Cooling 22 C Heating 28 C Note While under the forced operation the temperature compensation schedule The forced ope...

Page 67: ...n Therefore the TIMER LED is activated similar to TIMER function 12 12 1 Adjustment in Sleep Mode 1 in cool auto cool or dry modes the SPT adjustment is positive from 0 to 3o c 2 In heat or auto heat...

Page 68: ...rting of Sleep the Sleep time is extended And instead of going to SB at the 7th hour the A C will work until reaching the Off time Case 3 is an exception to case 2 The Sleep Mode will not be extended...

Page 69: ...12 27 CONTROL SYSTEM SM DELTA 1 E 0 GB 12 13 Clogged Air Filter Filter LED ON after 512 HR Filter LED is turned OFF and the Filter Timer is restarted by pressing the reset button...

Page 70: ...INDOOR FAN SPEED TEST SELF TEST FLOW CHART Step 1 Step 2 Step 3 FOR CONTROLLER VERSION 4V5 OR HIGHER COOL HEAT COMPRESSOR OUTDOOR FAN R V LOW MEDIUM HIGH TIMER OPERATE STANDBY BUZZER TEST ONE BEEP SOU...

Page 71: ...AN no I FEEL Sleep or any other timer settings Uncover the remote control IR transmitter and change the temperature settings If the display indoor unit receive the settings properly the following step...

Page 72: ...lly f STEP 6 FREQUENCY TESTING If the frequency measuring process fails the COOL LED will turn ON In order to move to the next step press ON OFF button on the remote control g STEP 7 INPUT TEST The te...

Page 73: ...c Values of Sensors Temperature VS Voltage DC Temp C Voltage V Temp C Voltage V Temp C Voltage V Temp C Voltage V 20 4 554 2 3 744 24 2 555 46 1 487 19 4 529 3 3 695 25 2 5 47 1 447 18 4 502 4 3 646 2...

Page 74: ...ks during Water Over Flow in MBX P2000 models COOLING INDICATOR Lights up when system is switched to Cool Mode by using the Mode Switch on the unit Show the thermistor status in Diagnostic Mode HEATIN...

Page 75: ...E before clock is changed CLOCK STATE before clock is changed CLOCK ACTION clock is changed A C NEW STATE after clock is changed ON 1 0 OFF OFF 0 1 ON OFF by interrupt 1 1 0 OFF ON by interrupt 1 0 1...

Page 76: ...conds according to the following table No Problem 1 RT1 is disconnected 2 RT1 is shorted 3 Reserved 4 RT2 is disconnected 5 RT2 is shorted 6 Reserved 7 RT2 temp reading doesn t change 8 RT3 is disconn...

Page 77: ...ctly Check the voltage between out door fan terminals on the main P C B There is voltage between outdoor fan terminals on the outdoor unit There is no voltage between outdoor fan terminals on the outd...

Page 78: ...ght enough on motor shaft tighten if necessary 13 Partial limited air supply at indoor unit Lack of refrigerant will accompanied by whistling noise cause ice formation on indoor unit coil in cooling m...

Page 79: ...14 1 EXPLODED VIEWS AND SPARE PARTS LISTS SM DELTA 1 E 0 GB 14 EXPLODED VIEWS AND SPARE PARTS LISTS 14 1 Indoor Unit DELTA 18 21 24...

Page 80: ...453024900 Impeller fan 1 13 453053800 Base assy WNG18 1 14 452920100 Mount bracket WNG 18 1 15 452919400 Joint Unit housing 1 16 453134300R Resin Motor 26W WNG24 LED DELTA21 24 1 453116500R Resin Moto...

Page 81: ...14 3 EXPLODED VIEWS AND SPARE PARTS LISTS SM DELTA 1 E 0 GB 14 3 Outdoor Unit GC 18 ST...

Page 82: ...ASSY 2 5mm2 1 17 4526922 heater for compressor 1 18 4516766 PAINTED VALVE PLATE ASSY 1 19 4526530 LOW PRESS VALVE R410A 1 20 4526531 High press valve R410A 1 21 4526931 filter welding assy 2 1 22 4526...

Page 83: ...14 5 EXPLODED VIEWS AND SPARE PARTS LISTS SM DELTA 1 E 0 GB 14 5 Outdoor Unit GC 18 RC...

Page 84: ...LVE PLATE ASSY 1 20 4526530 LOW PRESS VALVE R410A 1 21 4526531 High press valve R410A 1 22 4526931 filter welding assy 2 1 23 4526839 filter welding assy 1 24 4523145 R lifter 1 25 4526840 Single way...

Page 85: ...14 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM DELTA 1 E 0 GB 14 7 Outdoor Unit GC 21 RC...

Page 86: ...mpressor 1 19 4516766 PAINTED VALVE PLATE ASSY 1 20 4526513 LOW PRESS VALVE R410A 1 21 4526514 Hight press valve R410A 1 22 452891100 Filter assy 1 1 23 452891200 Filter assy 2 1 24 4523145 R lifter 1...

Page 87: ...14 9 EXPLODED VIEWS AND SPARE PARTS LISTS SM DELTA 1 E 0 GB 14 9 Outdoor Unit GC 21 ST...

Page 88: ...ESSOR WIRE ASSY 2 5mm2 1 17 452988900 Heater for compressor 1 18 4516766 PAINTED VALVE PLATE ASSY 1 19 4526513 LOW PRESS VALVE R410A 1 20 4526514 Hight press valve R410A 1 21 452891100 Filter assy 1 1...

Page 89: ...14 11 EXPLODED VIEWS AND SPARE PARTS LISTS SM DELTA 1 E 0 GB 14 11 Outdoor Unit GCN 12 RC...

Page 90: ...345 COMPRESSOR WIRE ASSY 2 5mm2 1 17 452892100 Heater for compressor 1 18 4516766 PAINTED VALVE PLATE ASSY 1 19 4526513 LOW PRESS VALVE R410A 1 20 4526514 Hight press valve R410A 1 21 452891100 Filter...

Page 91: ...14 13 EXPLODED VIEWS AND SPARE PARTS LISTS SM DELTA 1 E 0 GB 14 13 Outdoor Unit GC 24 RC...

Page 92: ...PLATE ASSY 1 20 4526513 LOW PRESS VALVE R410A 1 21 4526514 Hight press valve R410A 1 22 452891100 Filter assy 1 1 23 452891200 Filter assy 2 1 24 4523145 R lifter 1 25 452891600 Single way welding as...

Page 93: ...14 15 EXPLODED VIEWS AND SPARE PARTS LISTS SM DELTA 1 E 0 GB 14 15 Outdoor Unit OU7 24 RC 1PH...

Page 94: ...OU7 24 1 10 433281 SIDE GUARD OU7 24 R410 1 11 436358 OU LEADING HANDLE 1 12 439342 MOTOR SUPPORT OU7 24 1 13 190443 HEATER CRANKCASE MITSUBISHI 1 14 433293 COMPRESSOR NN27VBAMT 1 15 433934 CAPILLARY...

Page 95: ...14 17 EXPLODED VIEWS AND SPARE PARTS LISTS SM DELTA 1 E 0 GB 14 17 Outdoor Unit OU7 24 ST 1PH...

Page 96: ...OTOR 86W 2S OU7 24 1 10 433281 SIDE GUARD OU7 24 R410 1 11 436358 OU LEADING HANDLE 1 12 439342 MOTOR SUPPORT OU7 1 13 190443 HEATER CRANKCASE MITSUBISHI CO 1 14 433293 COMPRESSOR NN27VBAMT 1 15 43384...

Page 97: ...14 19 EXPLODED VIEWS AND SPARE PARTS LISTS SM DELTA 1 E 0 GB 14 19 Outdoor Unit OU7 24Z RC ST 1PH RSWLRQDO 20 19a 18 17 24 44...

Page 98: ...4 AXIAL FAN D493x143 1 9 434211 Replace by SP000000266 MOTOR BRACKET 1 10 433281 SIDE GUARD OU7 24 R410 1 11 436358 TRANSPORT HANDLE CUE 1 12 439342 MOTOR BASE OU7 1 14 438795 COMPRESSOR GP270PAA 1 15...

Page 99: ...14 21 EXPLODED VIEWS AND SPARE PARTS LISTS SM DELTA 1 E 0 GB 14 21 Outdoor Unit OU7 24 RC 3PH...

Page 100: ...062 MOTOR 86W 2S OU7 24 1 10 433281 SIDE GUARD OU7 24 R410 1 11 436358 OU LEADING HANDLE 1 12 439342 MOTOR SUPPORT OU7 1 13 190443 HEATER CRANKCASE MITSUBISHI CO 1 14 433753 COMPRESSOR NN27YDAMT 1 15...

Page 101: ...14 23 EXPLODED VIEWS AND SPARE PARTS LISTS SM DELTA 1 E 0 GB 14 23 Outdoor Unit OU7 24 ST 3PH...

Page 102: ...2 MOTOR 86W 2S OU7 24 1 10 433281 SIDE GUARD OU7 24 R410 1 11 436358 OU LEADING HANDLE 1 12 439342 MOTOR SUPPORT OU7 1 13 190443 HEATER CRANKCASE MITSUBISHI CO 1 14 433753 COMPRESSOR NN27YDAMT 1 15 43...

Page 103: ...de no RCW 436195 WNG add PCB SP000000290 ENGLISH REMOTE CONTROL 1 START STOP button 2 Operation modeselection button COOLING HEATING AUTO COOL HEAT DRY FAN 3 LOCAL temperaturesensing button 4 FAN SPEE...

Page 104: ...0000290 1 2 3 4 1 Display screen 2 Keys for raising and lowering the set temperature 3 Ventilation mode selection Low speed Medium speed High speed AUTO Automatic speed selection 4 ON Standby Accessin...

Page 105: ...on site in case the working conditions are below the standard operating range of the unit in cooling mode The ASK allows working in cooling at low temp up to 10 C for rooms with high internal gains F...

Page 106: ...15 4 OPTIONAL ACCESSORIES SM DELTA 1 E 0 GB...

Page 107: ...15 5 OPTIONAL ACCESSORIES SM DELTA 1 E 0 GB...

Page 108: ...15 6 OPTIONAL ACCESSORIES SM DELTA 1 E 0 GB...

Page 109: ...15 7 OPTIONAL ACCESSORIES SM DELTA 1 E 0 GB...

Page 110: ...16 1 APPENDIX A SM DELTA 1 E 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL INSTALLATION AND OPERATION MANUAL DELTA 18 21 24...

Reviews: