Components
Service manual
268
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
3.21.2 Repair procedures
To remove the user interface
1
See relevant manual of the user interface (remote controller) for the correct
procedure.
2
To intall the user interface, see
268].
To install the user interface
1
See relevant manual of the user interface (remote controller) for the correct
procedure.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To adjust the settings
1
See the relevant documentation (installer reference guide, remote controller
manual, …) to adjust the specific setting.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To install the software
1
Install the software using the Updater Tool. See the Business Portal (
) for more information about the Updater Tool.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
3.22 Water flow sensor
3.22.1 Checking procedures
To perform an electrical check of the water flow sensor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
230].
1
Turn ON the power of the unit.
2
Activate
Installer
on the user interface. See the installer reference guide
for the correct procedure.
3
Go to
Actuator test run
via the user interface.