Troubleshooting
Service manual
48
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Trigger
Effect
Reset
Outdoor heat exchanger
thermistor input is out of
range.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
the
heat
exchanger
thermistor.
See
Possible cause:
Faulty heat exchanger thermistor.
2
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.53 J6-07 – Outdoor unit: Malfunction of heat exchanger thermistor
Trigger
Effect
Reset
Heat exchanger
thermistor input is out of
range.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the heat exchanger (middle) thermistor. See
Possible cause:
Faulty heat exchanger (middle) thermistor.
2
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.54 J6-32 – Leaving water temperature thermistor abnormality (outdoor unit)
Trigger
Effect
Reset
Temperature sensor after
plate type heat exchanger
is broken.
Unit will NOT stop
operating.
Automatic reset.