Are the measured voltages of the
backup heater contactor correct?
Action
Yes
heater and continue with the next
procedure.
No
Continue with the next step.
5
Measure the operating voltage on the contactor.
Is the measured operating voltage of
the backup heater contactor correct?
Action
Yes
Replace the specific backup heater
contactor(s), see
No
Check for the reason of faulty operating
voltage (broken wiring, faulty contact,
…), see
314].
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Repair procedures
To remove the backup heater
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
230].
1
Drain water from the water circuit, see
302].
2
Remove
the
backup
heater
thermal
protector,
see
3
Unscrew and remove the air purge valve. Keep for reuse.
4
Loosen and remove the screw from the pipe clamp.