Components
Service manual
182
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
d
e
a
b
c
a
L1C
b
L2C
c
L3C
d
Connector X801A
e
Connector X802A
Is the measured voltage on the PCB
correct?
Action
Yes
continue with the next procedure.
No
Continue with the next step.
5
Measure the output voltage between the phases L1B‑L2B‑L3B on the noise
filter PCB.
Result:
All measurements MUST be 400 V AC ± 10%.
6
Measure the output voltage on connectors X601 and X602 on the noise filter
PCB.
Result:
The measured voltages MUST be 230 V AC ± 10%.