Troubleshooting
Service manual
40
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Clean the outdoor heat exchanger. See
Possible cause:
Dirty outdoor heat exchanger.
2
Check that all stop valves of the refrigerant circuit are open. See
286].
Possible cause:
Closed stop valve in the refrigerant circuit.
3
Check the outdoor temperature. See
Possible cause:
Outdoor temperature is out of operation range.
4
Check the required space around the outdoor unit heat exchanger. See
Possible cause:
Insufficient air flow or air by‑pass due to required space
specifications not met.
5
Perform
a
check
of
the
heat
exchanger
thermistor.
See
Possible cause:
Faulty heat exchanger thermistor.
6
Perform a check of all expansion valves. See
Possible cause:
Faulty expansion valve.
7
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
8
Check if the refrigerant circuit is correctly charged. See
286].
Possible cause:
Refrigerant overcharge.
9
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
10
Check if the refrigerant circuit is clogged. See
286].
Possible cause:
Clogged refrigerant circuit.
11
Perform a check of the outdoor unit fan motor. See
Possible cause:
Faulty outdoor unit fan motor.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.40 H0-00 – Outdoor unit: Voltage/current sensor problem
Trigger
Effect
Reset
Compressor voltage (DC)
is out of range before
start‑up.
Unit will stop operating.
Manual reset via user
interface.