![background image](http://html.mh-extra.com/html/daikin/altherma/altherma_service-manual_501166255.webp)
3
|
Components
Service manual
255
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
To perform an electrical check of the specific thermistor
1
First perform a mechanical check of the thermistor, see
254].
2
Locate the thermistor.
INFORMATION
Remove the thermistor from its holder if not reachable with a contact thermometer.
3
Measure the temperature using a contact thermometer.
Name
Symbol
Location
(PCB)
Connector
(pins)
Inter-
mediate
terminal
(wires)
Referen
ce
(table)
Outlet
water after
plate type
heat
exchanger
thermistor
R1T
Hydro
X5A: 1‑2
–
A
Outlet
water after
backup
heater
thermistor
R2T
Hydro
X6A: 1‑2
For units
with built‑in
backup
heater: -
A
For units
with backup
heater kit:
▪
X5M: 1‑2
▪
X15M: 1‑2
A
Inlet water
thermistor
R4T
Hydro
X8A: 1‑2
–
A
Domestic
hot water
tank
thermistor
(ONLY with
optional
domestic
hot water
tank
installed)
R5T
Hydro
X9A: 1‑2
–
For
domest
ic hot
water
tank
EKHWP
: A
For
domest
ic hot
water
tank
EKHWS
or third
party
domest
ic hot
water
tank: B