Service manual
251
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
5
Disconnect the thermistor connector from the appropriate PCB.
6
Measure the resistance between the appropriate pins of the thermistor
connector.
7
Check that the measured resistance value matches the resistance determined
through the measured temperature (earlier step in the procedure).
▪
E.g. R1T thermistor:
▪
Measured temperature with contact thermometer: 23.1°C,
▪
Resistance value determined through temperature (using the thermistor
table A):
Resistance at 23°C: 21.85 kΩ,
Resistance at 24°C: 20.90 kΩ,
▪
Disconnect connector and measure resistance between X11A pin 1‑3:
Measured resistance: 21.86 kΩ,
▪
Measured resistance value is inside the range. R1T thermistor passes the
check.
INFORMATION
All thermistors have a resistance tolerance of 3%.
INFORMATION
In most cases, the user interface allows to monitor the thermistors.
If the measured resistance value matches the resistance determined through the
measured temperature, but the temperature for the corresponding thermistor is
NOT correct on the user interface display, replace the applicable PCB.
Does the measured resistance of the
thermistor match with the
temperature determined resistance?
Action
Yes
Thermistor is OK. Return to the
troubleshooting of the specific error
and continue with the next procedure.
No
Replace the specific thermistor, see
Repair procedures
To remove the thermistor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Locate the thermistor that needs to be removed.
2
Remove the thermistor from the thermistor holder as follows:
▪
For air (ambient) thermistor:
Open the thermistor holder and remove the thermistor from the holder.
▪
For refrigerant piping thermistors:
- Cut the tie straps that fix the insulation and the thermistor wire.
- Cut and remove the insulation.
- Pull the clip that fixes the thermistor.
- Remove the thermistor from the thermistor holder.