3
|
Components
Service manual
185
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Prerequisite:
Turn OFF the respective circuit breaker.
1
Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2
Check that no connectors or wires are damaged.
3
Check that the wiring corresponds with the wiring diagram, see
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
181] of the PCB and
continue with the next procedure.
To check the fuse of the main PCB
Prerequisite:
First perform all earlier main PCB checks, see
181].
1
Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
a
a
Fuse F7U
Blown fuse on the main PCB?
Action
Yes
Replace the blown fuse, see
190].
No
Return to
181] of the main PCB
and continue with the next procedure.
To check the rectifier voltage of the main PCB
Prerequisite:
First perform all earlier main PCB checks, see
181].
1
Turn ON the power of the unit.