3
|
Components
Service manual
128
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
a
b
a
Backup heater thermal protector sensor
b
Backup heater
b
c
a
a
c
d
a
Screw
b
Backup heater thermal protector bracket
c
Screw
d
Backup heater thermal protector
3
Connect the wires to the wire terminals at the back of the backup heater
thermal protector.
4
Install the backup heater thermal protector on the bracket. Install and tighten
the 2 screws.
5
Install the backup heater thermal protector bracket on the switch box. Install
and tighten the 2 screws.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.