3
|
Components
Service manual
271
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
5
Remove the 2 clips that fix the water flow sensor.
6
Remove the water flow sensor.
7
Clean any spilled water.
8
To install the new water flow sensor, see
To install the water flow sensor
CAUTION
Check the condition of the O-rings and replace if needed. Apply water to the O-rings
before installation.
1
Mount the O-rings on the water flow sensor.
2
Install the water flow sensor on the inlet pipe. Ensure that the O-ring does
NOT get damaged.
3
Slide the clip over the connection until it snaps into place.
c
a
b
b
a
Water flow sensor connector nut
b
Clip
c
Water flow sensor
4
Install the water flow sensor on the outlet pipe. Ensure that the O-ring does
NOT get damaged.
5
Slide the clip over the connection until it snaps into place.
6
Connect the water flow sensor harness to the water flow sensor.
7
Tighten the water flow sensor connector nut.
INFORMATION
Replace all cable ties that were cut during removal.
8
Open the valve (if equipped) of the water circuit towards the expansion vessel.
CAUTION
Make sure to open the valve (if equipped) towards the expansion vessel, otherwise
the overpressure will be generated.
9
Open the stop valves and add water to the water circuit if needed, see