Troubleshooting
Service manual
57
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.68 U0-00 – Outdoor unit: Shortage of refrigerant
Trigger
Effect
Reset
Refrigerant shortage
detected.
Unit will stop operating.
Automatic reset.
Power reset via outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
all
refrigerant
side
thermistors.
See
248].
Possible cause:
Faulty refrigerant side thermistor(s).
2
Perform a check of the refrigerant pressure sensor. See
Possible cause:
Faulty refrigerant pressure sensor.
3
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
4
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
5
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant shortage.
6
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
286].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
7
Perform a check of the compressor. See
134].
Possible cause:
Faulty compressor or miswiring of the compressor power
supply cable.
8
Perform a check of all expansion valves. See
149].
Possible cause:
Faulty expansion valve.
9
Check for leaks in the refrigerant circuit. Look for oil traces on the unit(s).
Check the brazing points on the field piping. Perform a pressure test, see
Possible cause:
Leak in the refrigerant circuit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.