3
|
Components
Service manual
136
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
INFORMATION
The compressor dampers may look different.
Compressor dampers are in a good
condition?
Action
Yes
Perform an electrical check of the
compressor, see
No
Replace the compressor and/or
damaged dampers, see
To perform an electrical check of the compressor
1
First perform a mechanical check of the compressor, see
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
285].
2
Remove the cover of the compressor wire terminals.
a
a
Compressor wire terminals cover
3
Disconnect the Faston connectors from the compressor wire terminals U, V
and W.
INFORMATION
Note the position of the Faston connectors on the compressor wire terminals to
allow correct connection during installation.