2
|
Troubleshooting
Service manual
23
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Possible cause:
Increased water temperature due to an external heat source.
5
Perform a check of the backup heater thermal protector. See
121].
Possible cause:
Faulty backup heater thermal protector.
6
Perform a check of the outlet water after backup heater thermistor. See
248].
Possible cause:
Faulty outlet water after backup heater thermistor.
7
Perform a check of the backup heater. See
104].
Possible cause:
Faulty backup heater.
8
Perform a check of the hydro PCB. See
160].
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.18 AC-00 – Booster heater overheated
Trigger
Effect
Reset
Thermal protection of
booster heater does NOT
have any feedback signal
anymore.
Error will be triggered
when bridge connection
over booster heater
contact is NOT made.
Manual reset via user
interface when bridge
connection is made.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check the water flow. See
299].
Possible cause:
Water flow is too low.
2
Purge the water circuit. See
299].
Possible cause:
Air in the water circuit.
3
Check the water circuit for an external heat source. See
Possible cause:
Increased water temperature due to an external heat source.
4
Check the domestic hot water tank and booster heater related settings. See
Possible cause:
Faulty booster heater settings.
5
Check that the bridge connector X21A of the hydro PCB is correctly
connected. See
160].
Possible cause:
Open jumper X21A on hydro PCB.
6
Perform a check of the booster heater thermal protector. See
133].
Possible cause:
Faulty booster heater thermal protector.