3
|
Components
Service manual
203
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
5
Pull the refrigerant pipe forward and install the main PCB mounting plate on
its correct location. Install and tighten the fixation screws.
INFORMATION
Make sure that the refrigerant pipe is correctly installed on the main PCB heat sink.
Do NOT touch the part of the refrigerant pipe that is mounted in the heat sink.
6
Install the heat sink cover. Close and slide it downwards to fix the 2 hooks.
7
Install and tighten the 3 screws so that the heat sink cover presses the
refrigerant pipe.
a
a
a
b
c
f
f
d
f
e
f
a
Heat sink cover screw
b
Heat sink cover
c
Wires U, V and W
d
Ground wire screw
e
Main PCB mounting plate
f
Main PCB mounting plate fixation screw
8
Connect the ground wires to the main PCB mounting plate and tighten the
screw.
9
Connect the U, V and W wires to the main PCB and tighten the screws.
10
Connect all connectors to the main PCB.
11
Fix the cables to the main PCB mounting plate using new tie straps.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
194] of the noise filter
PCB and continue with the next
procedure.