3
|
Components
Service manual
143
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
a
a
a
Compressor pipe
7
Stop the nitrogen supply when the piping has cooled down.
INFORMATION
It is ALSO possible to cut the component pipe(s) using a pipe cutter. Make sure to
remove the remaining component pipe end(s) from the refrigerant pipes by heating
the brazing point(s) of the component pipe(s) using an oxygen acetylene torch.
8
Remove the nuts and bolts and remove the compressor from the unit.
b
a
c
a
c
a
Nut
b
Compressor
c
Damper
9
Remove the 3 dampers from the compressor.
INFORMATION
The compressor dampers may look different.
10
Remove the bushings and keep them for re-use.
11
Install plugs or caps on the open pipe ends of the refrigerant piping to avoid
dirt or impurities from entering the piping.
12
To install the compressor, see
To install the compressor
1
Check the state of the dampers. Replace if worn.
2
Install the 3 dampers in the correct location on the unit.