3
|
Components
Service manual
233
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
g
a
c
b
d
d
d
d
f
h
h
h
e
e
e
e
e
a
Electrical power supply wiring
b
Faston connectors (power supply towards hydro box)
c
Service port
d
Connector
e
Tie strap
f
DC fan motor harness
g
Wire clip
h
Compressor wiring
5
Remove the bolt to disconnect the service port from the switch box.
6
Disconnect the indicated connectors from the main PCB.
7
Remove the screw and disconnect the ground wire from the switch box (lower
right corner).
8
Cut the tie straps that fix the wiring to the switch box.
9
Remove the DC fan motor harness from the wire clip and leave it aside.
10
Remove the screws and disconnect the compressor wiring from the main PCB.
11
Disconnect the compressor thermal protector connector.
12
Route all wiring on the upper right side of the switch box through the hole
towards the back side of the switch box.
13
Route the 4‑way valve and high pressure switch wiring harness through the
holes towards the back side of the switch box.
14
Remove all wiring from the wire clips on the back side of the switch box.