3
|
Components
Service manual
269
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
4
Activate the
Pump
.
5
Select
Flow rate
.
Result:
The displayed flow rate MUST be 5~60 l/min.
6
Measure the water flow with a calibrated external flow meter.
7
Measure the frequency on connector X34A between pins 2‑3 (= flow sensor
output signal) on the hydro PCB.
INFORMATION
The flow sensor connector MUST be plugged into X34A on hydro PCB.
8
Using the following formula, calculate the water flow rate:
Flow rate [l/min] = (output frequency [Hz]x0.3)−1.2
INFORMATION
There is an offset of 4 Hz. If the water flow is 0 l/min (pump is NOT running), the
frequency output of the water flow sensor is 4 Hz.
9
Check that the calculated water flow rate is in line with the measured water
flow.
INFORMATION
In most cases, the user interface allows to monitor the water flow.
If the calculated water flow matches the measured water flow, but the water flow is
NOT correct on the user interface display, replace the applicable PCB.
Do the measured and calculated water
flow match?
Action
Yes
Water flow sensor is OK. Return to the
troubleshooting of the specific error
and continue with the next procedure.
No
Continue with the next step.
10
Unplug the water flow sensor connector X34A and measure the voltage
(power supply) between pins 1‑2 on hydro PCB.
Result:
The measured voltage MUST be +5 V DC.
Is measured v5 V DC?
Then
Yes
Continue with the next step.
No
Perform a check of the hydro PCB, see
160].
11
Disconnect the water flow sensor harness from the water flow sensor and
from the connector X34A. Measure the continuity of the wiring harness.
Is continuity of the wiring harness
correct?
Action
Yes
Replace the water flow sensor, see
270].
No
Replace the water flow sensor harness,
see
270].