3
|
Components
Service manual
232
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Prerequisite:
Stop the unit operation via the user interface.
1
Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2
Remove the discharge grille, see
230].
3
Loosen and remove the screws that fix the top plate.
a
a
a
b
a
a
a
a
a
a
a
a
Screw
b
Top plate
4
Remove the top plate.
3.17.4 To remove the switch box
Single phase unit
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
230].
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
285].
2
Remove the protective cover sheet.
3
Disconnect the electrical power supply wiring from the wire terminal.
4
Disconnect the Faston connectors (power supply towards hydro box) from the
wire terminal.