2
|
Troubleshooting
Service manual
81
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Root cause category: component – electrical
Possible failure
Root cause
Check
Repair
Outlet water after backup
heater thermistor
deviation causes incorrect
temperature control.
▪
Deviation of thermistor
(lower
temperature
measured than actual),
▪
Bad contact between
sensor and pipe.
Check outlet water after
backup heater thermistor.
Replace outlet water after
backup heater thermistor
or hydro PCB.
Deviation of domestic hot
water tank thermistor.
(Remark: ONLY valid for
inaccurate domestic hot
water temperature
control.)
▪
Deviation of thermistor,
▪
Bad contact between
sensor and pipe.
Check domestic hot water
tank thermistor.
Replace domestic hot
water tank thermistor or
hydro PCB.
User interface –
thermostat sensor has
incorrect reading of room
temperature.
Deviation of user interface
room temperature sensor.
Compare temperature
measured by user interface
with actual room
temperature.
In case of deviation the
room temperature offset
can be adjusted through
setting [2‑0A].
2.4.13 Symptom: Power consumption too high
Root cause category: end user
Possible failure
Root cause
Check
Repair
Too high domestic hot
water setpoint.
User set too high domestic
hot water setpoint by
schedule or manual
operation.
Check domestic hot water
tank set temperature;
avoid electric heater use.
Adapt domestic hot water
setpoint (e.g. 50~55°C).
Too high leaving water
temperature setpoint.
User set too high leaving
water temperature
setpoint by schedule or
manual operation.
Check leaving water
setpoint.
Adapt leaving water
setpoint (e.g. <55°C will
reduce backup heater
operation).
Too high space heating
setpoint on room
thermostat.
User set too high room
setpoint by schedule or
manual operation.
Check room thermostat
setpoint.
Adapt room thermostat
setpoint.
Root cause category: parameter (setting)
Possible failure
Root cause
Check
Repair
Too high leaving water
temperature (LWT) -
weather dependent.
Incorrect weather
dependent setting --> too
high LWT limit set
[1‑00]~[1‑09].
Check leaving water
temperature (LWT) high
limit in weather dependent
(setting [1‑03]).
Adapt high leaving water
temperature (LWT) limit
for weather dependent
heating (setting [1‑03]).
User interface thermostat
used with setting [C‑07] on
value 1 (= external
thermostat control).
Wrong setting of [C‑07] -
unit control method.
Check setting [C‑07].
Adjust setting to match
application - see installer
reference guide.