2
|
Troubleshooting
Service manual
17
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
6
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge.
7
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
8
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
286].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
9
Check the water flow. See
299].
Possible cause:
Water flow is too low.
10
Check the water pressure. See
299].
Possible cause:
Water pressure is too low.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.9 89-02 – Heat exchanger frozen
Trigger
Effect
Reset
Condensing temperature
<0°C during space
heating.
Unit will stop operating.
Automatic reset.
Liquid refrigerant
thermistor ≤0°C during
space heating or domestic
hot water.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the 4‑way valve. See
Possible cause:
Faulty 4‑way valve.
2
Perform a check of the main PCB. See
171].
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.