C200H AC Servo Manual
70
2:Analog torque internal torque
command:
DI Signal
Torque Command
TRQ2
TRQ1
0
0
Analog Torque Command
0
1
Internal Torque2(PA65)
1
0
Internal Torque3(PA66)
1
1
Internal Torque4(PA67)
Note: 0 means off ,1 means on.
33
The input
direction
of analog
torque
command
Reverse the input polarity of analog torque.
0-1
0
34
Internal
CCW
torque
limit
1.The setting value is the percentage of rated
torque.For example,it is set to 2 times of the rated
torque, the value is 200.
2. At any time, this restriction is valid.
3. If the setting value is over than the max overload
capacity, the actual torque limit is the max overload
capacity that is permitted.
0-300%
300
35
Internal
CW torque
limit
1.The setting value is the percentage of rated
torque.For example,it is set to 2 times of the rated
torque, the value is 200.
2. At any time, this restriction is valid.
3. If the setting value is over than the max overload
capacity, the actual torque limit is the max overload
capacity that is permitted.
-300-0%
-300
36
External
CCW
torque
limit
1.The setting value is the percentage of rated torque,
for example, it is set to 1 time of rated torque, the
value is 100.
2.Only when the input terminal(FIL) of CCW torque
limit is ON is it valid.
0-300%
100
Summary of Contents for C200H Series
Page 1: ...https en coolmay com ...
Page 2: ...C200H AC Servo Manual https en coolmay com ...
Page 43: ...C200H AC Servo Manual 36 Pic 4 17 Ground Connection Handling Of Noise Filter ...
Page 52: ...C200H AC Servo Manual 45 5 2 2 Speed Mode Wiring 三相 Pic5 4 Speed Mode Wiring ...
Page 55: ...C200H AC Servo Manual 48 5 3 2 Torque Mode Wiring Pic5 6 Torque Mode Wiring ...