C200H AC Servo Manual
105
No.
Alarm
name
Running
state
Reason
Processing method
9
IPM
module
failure
Appears when
the control
power is
turned on
Circuit board failure.
Replace the servo driver.
Appears during
motor
operation
1. The power supply
voltage is low.
2. Overheating.
1. Check the drive.
2. Power on again.
3. Replace the drive.
Short circuit between driver
and UVW.
Check the wiring.
Poor grounding.
Properly grounded.
The motor insulation is
damaged.
Replace the motor.
Disturbed.
1. Add line filter.
2. Keep away from
interference sources.