C200H AC Servo Manual
79
3. The comparator has hysteresis function set by
PA86.
4. Use this function in case that in near
positioning, the host controller is accepting the
NEAR signal to carry on the preparation to the
next step. In general, this parameter value
should be bigger than PA16.
86
Hysteresis for
approach
positioning
Refer to parameter PA85.
0-32767
pulses
650
87
Hysteresis of
arrival speed
1. When the motor speed exceeds this parameter,
the digital output ASP ( speed arrival) is ON,
otherwise OFF.
2. The comparator has hysteresis function.
3. It has polarity setting function:
PA88
PA28
Comparator
0
>0
Speed without direction
1
>0
Only detect positive speed
<0
Only detect reversal speed
0-5000
r/min
30
88
Polarity of
arrival speed
Refers to parameter PA87.
0-1
0
89
Arrival torque
1. When the motor torque exceeds this parameter,
the digital outputATRQ ( torque arrival) is ON,
otherwise OFF.
2. The comparator has hysteresis function set
by PA90.
3. It has polarity setting function:
PA91
PA89
Comparator
0
>0
Torque without direction
1
>0
Only detect positive speed
<0
Only detect reversal speed
-300%-
300%
100
90
Hysteresis of
arrival torque
1.If the motor torque is bigger than PA90, the
ATRQ( torque arrival) of digital output(DO) is
0-300%
5
Summary of Contents for C200H Series
Page 1: ...https en coolmay com ...
Page 2: ...C200H AC Servo Manual https en coolmay com ...
Page 43: ...C200H AC Servo Manual 36 Pic 4 17 Ground Connection Handling Of Noise Filter ...
Page 52: ...C200H AC Servo Manual 45 5 2 2 Speed Mode Wiring 三相 Pic5 4 Speed Mode Wiring ...
Page 55: ...C200H AC Servo Manual 48 5 3 2 Torque Mode Wiring Pic5 6 Torque Mode Wiring ...