Connecting the Aftercooler and
Optional Precooler
(W1300 - 5000)
The aftercooler and/or optional precooler require a source of city, tower, or chiller water
and a discharge or return line. You can use water at temperatures of 45 to 85°F {7 to
29°C}.
1
Connect the water supply line to
the aftercooler or precooler inlet.
If a manual shut off valve is used,
it should be mounted on the inlet
line. Conair recommends that a
manual shut off valve be used on both
the supply and return lines.
2
Connect the water discharge or
return line to the aftercooler
or precooler outlet.
IMPORTANT:
Turn the water off when the dryer is
not in use to prevent condensation.
aftercooler inlet
aftercooler outlet
✒
TIP:
Make the water supply
and discharge / return con-
nections with flexible hoses
at least 24 in. (61 cm) long.
This allows you to easily
remove the aftercooler
assembly for cleaning.
Recommended Water Flow Rates
Dryer Model
gal./min. {liters/min.}
600 15 {56.8}
800 15 {56.8}
1000 20 {75.7}
1300 25 {94.6}
1600 25 {94.6}
2000 25 {94.6}
2400 25 {94.6}
3200 30 {113.6}
4000 30 {113.6}
5000 30 {113.6}
IMPORTANT:
If an optional
flow control is also being
installed with the aftercool-
er, the manual shut off
valve should be installed
on the inlet line for the flow
control.
Summary of Contents for Carousel Plus UGD043-1216
Page 7: ...Table of Contents l v...
Page 8: ...vi l Table of Contents...
Page 48: ...3 24 l Installation Testing...
Page 54: ...4 6 l Operation Control Function Flow Charts continued Login Flow Chart...
Page 55: ...4 O p e r a t i o n Operation l 4 7 Operation Basic Controls...
Page 56: ...4 8 l Operation Control Function Flow Charts continued Operation Flow Chart 1 continued...
Page 58: ...4 10 l Operation...
Page 59: ...Operation Dew Point Package Controls 4 O p e r a t i o n Operation l 4 11...
Page 60: ...Control Function Flow Charts continued Operation Flow Chart 1 4 12 l Operation...
Page 62: ...4 14 l Operation...
Page 63: ...4 O p e r a t i o n Operation l 4 15 Operation Setup Control...
Page 64: ...4 16 l Operation Control Function Flow Charts continued continued Setup Flow Chart 1...
Page 66: ...4 18 l Operation continued Control Function Flow Charts continued Equipment Setup Flow Chart 2...
Page 164: ...6 46 l Troubleshooting...