Tr o u b l e s h o o t i n g l
6-9
Problem
Regeneration Blower
Overload
- If the regenera-
tion blower exceeds its full
load amp rating or the over-
load has tripped due to a
mechanical or electrical prob-
lem the dryer will shut down.
The default setting for this
alarm is passive but it can be
changed to shutdown.
Possible cause
The regeneration blower current draw
has exceeded the full load amps rating
of the motor.
The regeneration blower has mechani-
cally failed or is unable to rotate freely.
The regeneration blower has failed
electrically.
Loss of phase of power to the motor
starter.
The overload is set incorrectly.
The overload is defective.
Solution
Press alarm acknowledge and allow the
overload to reset then try to restart the
dryer. If the alarm condition occurs
again have a qualified electrician check
the current draw to the motor.
Disconnect and lock out main power.
Check the regeneration blower for
mechanical failure and free rotation.
Replace if necessary. Allow the over-
load to reset then try to restart the
dryer.
Disconnect and lock out main power.
Check the regeneration blower for elec-
trical shorts or open circuits. Replace if
necessary. Allow the overload to reset
then try to restart the dryer.
Check for a blown fuse in the dryer or
main power supply. Allow the overload
to reset then try to restart the dryer.
Disconnect and lock out main power.
Check the overload settings and
confirm that the settings match the full
load amps listed on the process blower
motor. Allow the overload to reset then
try to restart the dryer.
Replace the overload.
Shutdown Alarms
If an alarm occurs, a red dialog box is displayed on the dryer’s touch screen
control. The dryer will shut down automatically to prevent damage to the
equipment or personnel. The dialog box will indicate whether the alarm is a
shut down alarm or a passive alarm.
Summary of Contents for Carousel Plus UGD043-1216
Page 7: ...Table of Contents l v...
Page 8: ...vi l Table of Contents...
Page 48: ...3 24 l Installation Testing...
Page 54: ...4 6 l Operation Control Function Flow Charts continued Login Flow Chart...
Page 55: ...4 O p e r a t i o n Operation l 4 7 Operation Basic Controls...
Page 56: ...4 8 l Operation Control Function Flow Charts continued Operation Flow Chart 1 continued...
Page 58: ...4 10 l Operation...
Page 59: ...Operation Dew Point Package Controls 4 O p e r a t i o n Operation l 4 11...
Page 60: ...Control Function Flow Charts continued Operation Flow Chart 1 4 12 l Operation...
Page 62: ...4 14 l Operation...
Page 63: ...4 O p e r a t i o n Operation l 4 15 Operation Setup Control...
Page 64: ...4 16 l Operation Control Function Flow Charts continued continued Setup Flow Chart 1...
Page 66: ...4 18 l Operation continued Control Function Flow Charts continued Equipment Setup Flow Chart 2...
Page 164: ...6 46 l Troubleshooting...