Appendix E - MODBUS Register Map
121
30122/40122
Overcurrent Trip Level
R/W
50 – 200
% RFA
30123/40123
Overcurrent Trip Delay Time
R/W
1 – 900
0.1 Sec
30124/40124
Undercurrent Trip Enable
R/W
0:
Disable
1:
Enable
—
30125/40125
Undercurrent Trip Level
R/W
5 – 99
% RFA
30126/40126
Undercurrent Trip Delay Time
R/W
1 – 900
0.1 Sec
30127/40127
Rated RMS Voltage
R/W
0:
100
1:
110
2:
120
3:
200
4:
208
5:
220
6:
230
7:
240
8:
320
9:
350
10:
380
11:
400
12:
415
13:
440
14:
460
15:
480
16:
500
17:
525
18:
575
19:
600
20:
660
21:
690
22:
800
23:
1000
24:
1140
Vrms
30128/40128
Over Voltage Trip Enable
R/W
0: Disable
1: Enable
—
30129/40129
Over Voltage Trip Level
R/W
1 – 40
%
30130/40130
Under Voltage Trip Enable
R/W
0:
Disable
1:
Enable
—
30131/40131
Under Voltage Trip Level
R/W
1 – 40
%
30132/40132
Over/Under Voltage Delay Time
R/W
1 – 900
0.1 Sec
30133/40133
Phase Loss Delay Time
R/W
1 – 50
0.1 Sec
30134/40134
High Line Freq. Trip Level
R/W
24 – 72
Hz
30135/40135
Low Line Freq. Trip Level
R/W
23 – 71
Hz
30136/40136
High/Low Line Freq. Delay Time
R/W
1 – 900
0.1 Sec
30137/40137
Auto Fault Reset Timer Enable
R/W
0:
Disable
1:
Enable
—
30138/40138
Auto Fault Reset Delay Time
R/W
1 – 900
Sec
30139/40139
Auto Fault Reset Cnt Enable
R/W
0:
Disable
1:
Enable
—
30140/40140
Auto Fault Reset Cnt
R/W
1 – 10
—
30141/40141
Input Phase Sensitivity
R/W
0:
AbC
1:
Cba
2:
InS
3:
SPH
—
30142/40142
Hall Effect Ratio (x:1)
R/W
0:
1000
1:
2000
2:
5000
—
30143/40143
Hall Effect Turns
R/W
1 – 10
—
Absolute Register
Address
Description
R/W
Range
Units
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...