6 - Parameter Descriptions
71
PFN 09 / P27
Phase Loss Time
LCD / LED
Displays
PFN: Ph Loss Time
09 0.2
sec
Range
0.1 – 5.0 seconds (Default: 0.2)
Description
The Phase Loss Time parameter sets the delay time on Fault 27 “Phase Loss”. This fault detects a loss of
proper phase timing even when the phasing remains valid; Example: loss of line when the motor back
generates a voltage
PFN 10 / P28
Over Frequency Level
LCD / LED
Displays
PFN: Over Frq Lvl
10 72
Hz
Range
24 – 72 Hz (Default: 72)
Description
The Over Frequency Level parameter sets the highest line frequency that the controller will operate on.
When operating on line power, the default setting will usually suffice. If the application is speed sensitive, or
the line power is suspect, the high frequency parameter can be set to the highest acceptable frequency. When
operating on generator power, the high frequency parameter should be set to the highest acceptable
frequency. This will ensure that a generator problem will not cause unnecessarily large fluctuations in the
speed of the motor.
The frequency must be above the high frequency setting for the frequency delay parameter before the
controller will recognize a high frequency condition. Once a high frequency condition exists, the controller will
shut down and display a fault 13, “High Line Frequency” Trip.
PFN 11 / P29
Under Frequency Level
LCD / LED
Displays
PFN: Undr Frq Lvl
11 23
Hz
Range
23 – 71 Hz (Default: 23)
Description
The Under Frequency Level parameter sets the lowest line frequency that the controller will operate on.
When operating on line power, the default setting will usually suffice. If the application is speed sensitive, or
the line power is suspect, the low frequency parameter can be set to the lowest acceptable frequency. When
operating on generator power, the low frequency parameter should be set to the lowest acceptable frequency.
This will ensure that a generator problem will not cause unnecessarily large fluctuations in the speed of the
motor.
The frequency must be below the low frequency setting for the frequency delay parameter before the controller
will recognize a low frequency condition. Once a low frequency condition exists, the controller will shut down
and display a Fault 12, “Low Line Frequency” Trip.
0
.2
72
23
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...