Wire Gauge:
The terminals can support 1–14 AWG wire or 2–16 AWG wires or smaller.
Torque Rating:
The terminals on the control cards have a torque rating of 5.0-inch lb. or 0.56Nm.
This MUST be followed or damage will occur to the terminals.
NOTE
: Refer to Control Card Layouts on Pages 29 and 30.
2.2.2 Measurements
and
Accuracies
Analog I/O
(Hall Effect
Input)
TB5
1: Ain
Power
2: M
3: Common
4: Ground
(Shield)
5: Aout
6: Common
7: Shield
Input:
Voltage or Current
Voltage:
0
–
10VDC, 67K
Ω
impedance
Current: 0
–
20mA, 500
Ω
impedance
Output:
Voltage or Current
Voltage: 0
–
10VDC, 120mA maximum
Current: 0
–
20mA, 500
Ω
load maximum
Display
RJ45
—
Door Mounted Display Connector
SCR
J6 to J11
1: Gate
2: Cathode
SCR Gate Connections
Table 1: Terminals (Continued)
Function
Terminal
Block
Terminal Number
Description
Table 2: Measurements and Accuracies
Internal Measurements
Hall Effect Input
Conversion:
True RMS, Sampling @ 1.562kHz
Range:
1 – 1000A
Line Voltage Inputs
Conversion:
True RMS, Sampling @ 1.562kHz
Range:
100 – 1,250VAC, 23 to 72 Hz
Metering
Current:
0 – 40,000 Amps ± 3%
Slip %
0.0 – 100%
Voltage:
0 – 1,250 Volts ± 3%
Line Frequency: 23 – 72 Hz ± 0.1 Hz
Run Time:
± 3 seconds per 24 hour period
Analog Input:
Accuracy ± 3% of full scale (10 bit)
Analog Output:
Accuracy ±2% of full scale (12 bit)
NOTE:
Percent accuracy is percent of full scale of the given ranges, Current = Motor FLA,
Voltage = 8,000V, Watts/Volts-Amps/Watt-Hours = Motor & Voltage range
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...