RediStart MX
2
- SEP Synchronous Controller User Manual
76
I/O 04 / P43
Digital Input Trip Time
LCD / LED
Displays
I/O: Din Trp Time
09 0.1
sec
Range
0.1
90.0 Seconds (Default: 0.1 Sec)
Description
The Digital Input Trip Time parameter sets the length of time that the digital input must be high or low before a
trip occurs. This delay time only functions for fault high and fault low.
See Also
• Digital Input Configuration parameters on Page 75.
I/O 5 - 7 / P44 - 46 Relay Output Configuration
LCD / LED
Displays
I/O: R1 Config
05 Interlock FS
I/O: R2 Config
06 FS1
I/O: R3 Config
07 Running
Range
LCD LED
Description
Off
OFF
Off, Not Assigned. May be controlled over Modbus
Fault FS
FLFS
Faulted – Fail Safe operation. Energized when no faults present,de-energized
when faulted.
Fault NFS
FLnF
Faulted– Non Fail Safe operation. Energized when faulted.
Interlock FS
SIFS
Interlock relay, fail safe operation. This relay will energize when the controller is
ready for a start command. The interlock relay must be used to interlock the
stator controller.
(Default R1)
Interlock NFS
SInF
Interlock relay, non fail safe operation. This relay will be energized when the
controller is not ready for a start command. The interlock relay must be used to
interlock the stator controller.
Running
run
Motor is running.
(Default R3)
Synced
SYnc
The controller has synchronized the motor.
Inching
inch
Controller is in inching mode.
Inch UTS
iutS
Controller is in inching mode and the inching UTS timer has expired.
Alarm
AL
Alarm, any alarm condition present.
Ready
rdYr
Ready, controller ready for start command.
Locked Out
LOC
Locked Out.
Overcurrent
OC
Overcurrent Alarm, overcurrent condition detected.
Undercurrent
UC
Undercurrent Alarm, undercurrent condition detected.
Shunt FS
ShFS
Shunt Trip Relay – Fail Safe operation, energized when no shunt trip fault present,
de-energized on shunt trip fault.
Shunt NFS
ShnF
Shunt Trip Relay – Non Fail Safe operation, de-energized when no
shunt trip fault
present, energized on shunt trip fault.
FS1
FS1
Used to control a field application contactor.
(Default R2)
FS2
FS2
Used to control a field discharge resistor contactor.
0
.1
SIFS
FS1
run
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...