6 - Parameter Descriptions
85
FUN 10 / P52
Com Address (Drop #)
LCD / LED
Displays
FUN: Com Drop #
10 1
Range
1 – 247 (Default: 1)
Description
The Communication Address parameter sets the controller’s address for Modbus communications.
See Also
• Local Source (QST 04 / P37) parameter on Page 61.
• Remote Source (QST 05 / P38) parameter on Page 61.
FUN 11 / P51
Communication Baudrate
LCD / LED
Displays
FUN: Com Baudrate
11 19200
Range
1200, 2400, 4800, 9600, 19200 bps (Default: 19200)
Description
The Communication Baud Rate parameter sets the baud rate for Modbus communications.
See Also
•
Local Source (QST 04 / P36) parameter on Page 61.
•
Remote Source (QST 05 / P37) parameter on Page 61.
FUN 12 / P50
Communication Timeout
LCD / LED
Displays
FUN: Com Timeout
12
Off
Range
Off, 1 – 120 (Default: Off)
Description
The Communication Timeout parameter sets the time that the controller continues to run without receiving a
valid Modbus request. If a valid Modbus request is not received for the time that is set, the controller declares a
F82 (Modbus Timeout Fault). The controller performs a controlled stop.
See Also
•
Local Source (QST 04 / P37) parameter on Page 61.
• Remote Source (QST 05 / P38) parameter on Page 61.
•
Stop Mode (CFN 05 / P10) parameter on Page 64.
• Controlled Fault Stop Enable (PFN 15 / P33) parameter on Page 73.
•
Communication parameters (FUN 10–13 / P50–53) on Pages 85–86.
1
OFF
19
.2
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...