RediStart MX
2
- SEP Synchronous Controller User Manual
102
8.4
Fault Code Table
The following is a list of possible faults that can be generated by the MX
2
SEP controller:
Fault Code
Description
Detailed Description of Fault / Possible Solutions
F01
Incomplete Sequence
Slip percentage (CFN 01 / P2) is set too low.
Incomplete Sequence Time (QST 03 / P6) is set too low.
F09
Loss of Synchronous
Slip percentage (CFN 01 / P2) is set too low.
Incomplete Sequence Time (QST 03 / P6) is set too low.
F12 Low
Line
Frequency
Line frequency below Setpoint (PFN11 / P29) was detected for longer than the
Freq Trip Time (PFN12 / P30).
Verify input line frequency.
If operating on a generator, check generator speed governor for malfunctions.
Check input supply for open fuses or open connections.
Line power quality problem / excessive line distortion.
F13
High Line Frequency
Line frequency above Setpoint (PFN10 / P28) was detected for longer than the
Freq Trip Time (PFN12 / P30).
Verify input line frequency.
If operating on a generator, check generator speed governor for malfunctions.
Line power quality problem / excessive line distortion.
F14
Input power not single phase
Three-phase power has been detected when the controller is expecting single-
phase power.
Verify that input power is single phase.
Verify that single-phase power is connected to the L1 and L3 inputs. Correct wiring
if necessary.
Verify that the SCR gate wires are properly connected to the MX2 SEP control
card.
F15
Input power not three phase
Single-phase power has been detected when the controller is expecting three-
phase power.
Verify that input power is three phase. Correct wiring if necessary.
Verify that the SCR gate wires are properly connected to the MX2 SEP control
card.
F21 Low
Line
L1-L2
Low voltage below the Under voltage Trip Level parameter setting (PFN07 / P25)
was detected for longer than the Over/Under Voltage Trip delay time (PFN08 /
P26).
Verify that the actual input voltage level is correct.
Verify that the Rated Voltage parameter (FUN06 / P23) is set correctly.
Check input supply for open fuses or open connections.
F22 Low
Line
L2-L3
Low voltage below the Under voltage Trip Level parameter setting (PFN07 P25)
was detected for longer than the Over/Under Voltage Trip delay time (PFN08 /
P26).
Verify that the actual input voltage level is correct.
Verify that the Rated Voltage parameter (FUN06 / P23) is set correctly.
Check input supply for open fuses or open connections.
F23 Low
Line
L3-L1
Low voltage below the Under voltage Trip Level parameter setting (PFN07 / P25)
was detected for longer than the Over/Under Voltage Trip delay time (PFN08 /
P26).
Verify that the actual input voltage level is correct.
Verify that the Rated Voltage parameter (FUN06 / P23) is set correctly.
Check input supply for open fuses or open connections.
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...