6 - Parameter Descriptions
81
FUN 00
Jump to Parameter
LCD Display
FUN: Jump Code
00 1
Description
By changing the value of this parameter and pressing [ENTER], you can jump directly to any parameter within
that group.
FUN 01- 02 / P17
Meter 1 - Meter 2
LCD / LED
Displays
FUN: Meter 1
01 Ave Current
FUN: Meter 2
02 Ave Volts
Range
LCD
LED
Description
Status
0
Running State.
(LED Meter only, Default LED meter)
Ave Current
1
DC field current.
(Default LCD Meter 1)
Ave Volts
2
Average Voltage L-L RMS.
(Default LCD Meter 2)
L1-L2 Volts
3
Voltage in, L1 to L2 RMS.
L2-L3 Volts
4
Voltage in, L2 to L3 RMS.
L3-L1 Volts
5
Voltage in, L3 to L1 RMS.
Slip Percent
6
The percentage of rotor slip.
Phase Order
7
Phase
rotation.
Line Freq
8
Line Frequency.
Analog Input
9
Analog Input %.
Analog Out
10
Analog Output %
Run Days
11
Running time in days, wraps at 2,750 days.
Run Hours
12
Running time in Hours and Minutes, wraps at 24:00.
Starts
13
Number of Starts, wraps at 65,536.
Description
For the LED display, this parameter configures which single meter is displayed on the main screen. For the
LCD display, parameters FUN 01 and FUN 02 configure which meters are displayed on the two lines of the
main display screen.
0
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...