5 - Parameter Groups
55
5.3
Parameter
Tables
LCD Parameters are subdivided into six groups: QST (Quick Start), CFN (Control Functions), PFN (Protection
Functions), I/O (Input/Output Functions), FUN (Function), and FL1 (Fault Log).
The Quick Start Group provides a collection of the parameters that are most commonly changed when
commissioning a controller. Many of the parameters in the Quick Start group are duplicates of the same
parameters in other groups.
The following tables show the menu structure for the LCD display, the corresponding LED code, as well as the
text displayed and pertinent information for each parameter.
If the LCD is not connected, parameters will only be shown on the MX
2
Control Card LED display.
5.3.1
Quick Start Group
5.3.2
Control Function Group
Table 16: Quick Start Parameter Group
Group
LED
Display
Parameter
Setting Range
Units
Default
Adjust
During
Run?
Page
Setting
QST 00
—
Jump Code
Jump to Parameter
1 – 5
—
1
–
60
QST 01
P1
Current Setpoint
Current Setpoint
1 – 1000
Amps
10
Y
60
QST 02
P3
Field Application Time
Field Application Time
OFF, 0.1 – 20.0
sec
OFF
Y
60
QST 03
P6
Incomplete Sequence Time
Incomplete Sequence Time
1 – 200
sec
30
Y
61
QST 04
P37
Local Control Source
Local Control Source
TEr
:Terminal
SEr
:Serial
—
Terminal
Y
61
QST 05
P38
Remote Control Source
Remote Control Source
TEr
:Terminal
SEr
:Serial
—
Terminal
N
61
Table 17: Control Function Group
Group
LED
Display
Parameter
Setting Range
Units
Default
Adjust
During
Run?
Page
Setting
CFN 00
—
Jump Code
Jump to Parameter
1 – 11
—
1
—
63
CFN 01
P2
Slip Percent
Slip Percentage
0.5 – 10.0
%
5.0
Y
63
CFN 02
P3
F Apply Dly
Field Application Delay Time
OFF, 0.1 – 20.0
sec
OFF
Y
63
CFN 03
P4
F Force Lvl
Field Forcing Level
50 – 125
%
120
Y
64
CFN 04
P5
F Force Time
Field Forcing Time
OFF, 0.1 – 90.0
sec
0.1
Y
64
CFN 05
P10
Stop Mode
Stop Mode
CoS
:Coast
DCB
:Dynamic Brake
—
Coast
N
64
CFN 06
P11
Brake Level
Dynamic Braking Level
10 – 125
%
25
Y
65
CFN 07
P12
Brake Time
Dynamic Braking Time
1 – 180
sec
5
Y
65
CFN 08
P13
Brake Delay
Dynamic Brake Delay
0.1 – 5.0
sec
0.5
Y
65
CFN 09
P14
Inch Field
Inch Field Level
75 – 125
%
100
Y
66
CFN 10
P15
Inch F App T
Inch Field Application Time
0.1 – 90.0
sec
2.0
Y
66
CFN 11
P16
Inch UTS Dly
Inch UTS Relay Delay Time
OFF, 0.1 – 90.0
sec
OFF
Y
66
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...