RediStart MX
2
- SEP Synchronous Controller User Manual
66
CFN 09 / P14
Inch Field Level
LCD / LED
Displays
CFN: Inch Field
09 100%
Range
75 – 125% (Default: 100%)
Description
The inching field level parameter sets the field current level that will be applied when the controller is in inching
mode. This current will be applied when a digital input programmed to “inch” is energized and the inch field
application delay time (CFN 10 / P15) has expired.
The inching is used to sequence the application of the field when the motor is being inched. The actual motor
inching is performed by the stator controller.
Inching operating sequence
See Also
•
Inch Field Application Time (CFN 10 / P15) on Page 66.
•
Inch UTS Delay (CFN 11 / P16) on Page 66.
•
Digital Inputs (I/O 01–03 / P40–42) on Page 75.
CFN 10 / P15
Inch Field Application Delay Time
LCD / LED
Displays
CFN: Inch F App T
10 2.0
Range
0.1 – 90.0 seconds (Default: 2.0)
Description
The Delay before Inching Field Application time delay sets the delay time between the “inching” digital input
being energized and the inching field current being applied to the motor.
NOTE:
See (CFN 09 / P14) for inching operating sequence.
CFN 11 / P16
Inch UTS Delay
LCD / LED
Displays
CFN: Inch UTS Dly
11 Off
Range
Off, 0.1 – 90.0 seconds (Default: Off)
Description
The Inch UTS delay starts timing after the inching field has been applied and delays the energizing of any relay
that is programmed as Inching UTS.
NOTE:
See (CFN 09 / P14) for inching operating sequence.
100
2
.0
OFF
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...