2 - Technical Specifications
17
2.2.3
List of Motor Protection Features
• ANSI 27 / 59 - Adjustable over/under voltage protection (Off or 1 to 40%, time 0.1 to 90.0 sec. in 0.1
sec. intervals, independent over and under voltage levels)
• ANSI 37 - Undercurrent detection (Off or 5 to 100% and time 0.1 to 90.0 sec. in 0.1 sec. intervals)
• ANSI 47 - Phase rotation (selectable ABC, CBA, Insensitive, or Single Phase)
• ANSI 48 - Adjustable up-to-speed / stall timer (1 to 900 sec. in 1 sec. intervals)
• ANSI 51 - Overcurrent detection (Off or 50 to 800% and time 0.1 to 90.0 sec. in 0.1 sec. intervals)
• ANSI 56 - Field Application
• ANSI 74 - Alarm relay output available
• ANSI 81 - Over / Under Frequency
• ANSI 95 - Reluctance torque sync
• ANSI 96 - Autoloading
• Single Phase Protection
• Shorted SCR Detection