RediStart MX
2
- SEP Synchronous Controller User Manual
32
3.8.3 Digital
Input
TB3 is for digital inputs Start, DI1, DI2 and DI3. These digital inputs use 120VAC. These digital inputs connect
as follows:
• 1 - Start: Start Input
• 2 - DI1: Digital Input 1
• 3 - DI2: Digital Input 2
• 4 - DI3: Digital Input 3
• 5 - Com: 120VAC neutral
Figure 9: Digital Input Wiring Examples
See Also
:
Digital Input Configuration (I/O 01 – 03 / P40-42) on Page 75.
120VAC LIVE
120VAC NEUTRAL
120VAC LIVE
120VAC NEUTRAL
START
DI1
DI2
DI3
120VAC LIVE
120VAC NEUTRAL
120VAC NEUTRAL
120VAC LIVE
120VAC NEUTRAL
FAULT RESET
DIGITAL INPUT WIRING
2-WIRE CONTACT CONTROL
FAULT RESET BUTTON
3-WIRE START / STOP BUTTONS
EXTERNAL TRIP INPUT
(DI2 SET TO Fr - FAULT RESET)
120VAC LIVE
TRIP
(DI3 SET TO FL - FAULT LOW)
START
STOP
TB3
TB3
TB3
TB3
TB3
(DI1 SET TO STOP)
M
M
M
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...