RediStart MX
2
- SEP Synchronous Controller User Manual
84
FUN 07 / P60
Rated Power Factor
LCD / LED
Displays
FUN: Rated PF
07 1.0
Range
-0.10 – +0.10 (Default: 1.0)
Description
The Rated Power Factor parameter sets the reference point for the PF controller algorithm. The PF will adjust
the field current to achieve this motor power factor
See Also
• Min PF Control Current (FUN 08 / P61) parameter on Page 84.
FUN 08 / P61
Min PF Control Current
LCD / LED
Displays
FUN: Min PF Curr
08 60%
Range
40% – 100% (Default: 60%)
Description
The Minimum Power Factor Control Current parameter sets the minimum field current that will be allowed when
operating in Power Factor Control Mode.
See Also
• Rated Power Factor (FUN 07 / P60) parameter on Page 84.
FUN 09 / P39
Control Type
LCD / LED
Displays
FUN: Control Type
09 Field Ctl
Range
LCD
LED
Description
Field Ctl
FcT1
Brush type motor field controller.
See Brushtype control in Section 7.1.1 on Page 89.
Brushless
bruS
Brushless type field controller.
See Brushless control in Section 7.1.2 on Page 90.
Curr Follow
cFoL
DC current controller
See Current Follower in Section 7.1.3 on Page 90.
PF Control
PF
Power Factor Control
See Power Factor Control in Section 7.1.4 on Page 91.
PF Control BL
PFbL
Power Factor Control - Brushless Motor
See Power Factor Control in Section 7.1.4 on Page 91.
NOTE
: Control Types are described in the Theory of Operation section beginning on Page 89.
1
.0
60
Fct1
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...