RediStart MX
2
- SEP Synchronous Controller User Manual
42
4.6
Jump Code
At the beginning of each parameter group, there is a Jump Code parameter. By changing the value of this
parameter and pressing
[ENTER], you can jump directly to any parameter within that group.
4.7
Restoring Factory Parameter Settings
To restore ALL parameters to the factory default settings, press and hold the [PARAM] and [ENTER]
pushbutton switch on power up. The display blinks “dFLt”. Parameters unique to the controller applications
need to be set again to appropriate values before motor operation.
P23 / FUN06 - Rated RMS Voltage (set to specified equipment rating) I/O 01 / P40 - Digital Input #1
P41 / I/O 02 - Digital Input #2
P42 / I/O 03 - Digital Input #3
P44 / I/O 05- Relay #1
P45 / I/O 06 - Relay #2
P46 / I/O 07 - Relay #3
NOTE
: Consult the wiring schematic for digital inputs and relay output configuration.
4.8
Resetting a Fault
To reset from a fault condition, press [RESET].
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...