4.13
Procedure for Setting Data
Select a parameter that is to be changed. To change the Current Setpoint from 10 Amps to 30 Amps:
From the main screen:
T Ready Ia = 0.0A
Stopped Va = 480V
Press [MENU] key, the display shows QST (Quick Start) screen.
QST: Jump Code
00 1
Press [UP] key once to access Motor FLA (QST 01).
QST: Cur Setpoint
01 10 Amp
Press [ENTER] key once, the cursor starts to flash in the “ones” place.
QST: Cur Setpoint
01 1
0
Amp
Press [LEFT] key once, the cursor flashes in the “tens” place.
QST: Cur Setpoint
01
1
0 Amp
Press [UP] arrow to increase the value, for a value of 30, press twice.
QST: Cur Setpoint
01
3
0 Amp
Press [ENTER] to store the value.
QST: Cur Setpoint
01 30 Amp
Press [UP] arrow to change another parameter in QST.
Press [MENU] to change another parameter in another group.
Press [LEFT] arrow to go back to the main screen.
3
1
0
Summary of Contents for RediStart MX2 SEP
Page 2: ......
Page 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Page 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Page 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Page 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Page 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Page 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Page 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Page 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Page 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Page 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...