DRV-28 inverter
s Function parameter list
-163-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P06.10
Relay RO1
switch-on delay
Setting range: 0.000–50.000s
Note: P06.08 and P06.09 are valid only when
P06.00=1.
0.000s
○
P06.11
Relay RO1
switch-off delay
0.000s
○
P06.12
Relay RO2
switch-on delay
0.000s
○
P06.13
Relay RO2
switch-off delay
0.000s
○
P06.14
AO1 output
selection
0: Running frequency
1: Set frequency
2: Ramps reference frequency
3: Running speed
4: Output current (relative to inverter)
5: Output current (relative to motor)
6: Output voltage
7: Output power
8: Set torque value
9: Output torque
10: AI1 input value
11: AI2input value
12: AI3 input value
13: Input value of high-speed pulse HDIA
14: Set value 1 of MODBUS communication
15: Set value 2 of MODBUS communication
16: Set value 1 of PROFIBUS\CANopen
communication
17: Set value 2 of PROFIBUS\CANopen
communication
18: Set value 1 of Ethernet communication
19: Set value 2 of Ethernet communication
20: Input value of high-speed pulse HDIB
21: Reserved
22: Torque current (bipolar, 100% corresponds to
10V)
23: Exciting current (100% corresponds to 10V)
24: Set frequency (bipolar)
25: Ramps reference frequency (bipolar)
26: Running speed (bipolar)
27: Set value 2 of EtherCat/Profinet communication
0
○
P06.15
Reserved
variables
0
○
P06.16
HDO high-speed
pulse output
0
○