DRV-28 inverter
s Function parameter list
-164-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
28: C_AO1 from PLC (You need to set P27.00 to 1.)
29: C_AO2 from PLC (You need to set P27.00 to 1.)
30: Running speed
31–47: Reserved
P06.17
Lower limit of
AO1 output
Above function codes define the relation between
output value and analog output. When the output
value exceeds the set max./min. output range, the
upper/low limit of output will be adopted during
calculation.
When analog output is current output, 1mA
corresponds to 0.5V voltage. In different
applications, 100% of output value corresponds to
different analog outputs.
10V (20mA)
0.0%
100.0%
AO
Setting range of P06.17: -100.0%–P06.19
Setting range of P06.18: 0.00V–10.00V
Setting range of P06.19: P06.17–100.0%
Setting range of P06.20: 0.00V–10.00V
Setting range of P06.21: 0.000s–10.000s
0.0%
○
P06.18
Corresponding
AO1 output of
lower limit
0.00V
○
P06.19
Upper limit of
AO1 output
100.0%
○
P06.20
Corresponding
AO1 output of
upper limit
10.00V
○
P06.21
AO1 output filter
time
0.000s
○
P06.22–
P06.26
Reserved
variables
0–65535
0
●
P06.27
Lower limit of
HDO output
-
100.0%–P06.29
0.00%
○
P06.28
Corresponding
HDO output of
lower limit
0.00–50.00kHz
0.00kHz
○
P06.29
Upper limit of
HDO output
P06.27–100.0%
100.0%
○
P06.30
Corresponding
HDO output of
upper limit
0.00–50.00kHz
50.00
kHz
○
P06.31
HDO output filter
time
0.000s–10.000s
0.000s
○
P06.32–
Reserved
0–65535
0
●