DRV-28 inverter
s Function parameter list
-183-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
and then convert 16-bit binary number into
hexadecimal number, finally, set corresponding
function code.
Acceleration/deceleration time 1 is set by P00.11
and P00.12; Acceleration/deceleration time 2 is set
by P08.00 and P08.01; Acceleration/deceleration
time 3 is set by P08.02 and P08.03; Acceleration
/deceleration time 4 is set by P08.04 and P08.05.
Setting range: 0x0000–0xFFFF
P10.36 PLC restart mode
0: Restart from the first step, namely if the inverter
stops during running (caused by stop command,
fault or power down), it will run from the first step
after restart.
1: Continue running from the step frequency when
interruption occurred, namely if the inverter stops
during running (caused by stop command or fault), it
will record the running time of current step, and
enters this step automatically after restart, then
continue running at the frequency defined by this
step in the remaining time.
0
◎
P10.37
Multi-step time
unit
0: s; the running time of each step is counted in
seconds;
1: min; the running time of each step is counted in
minutes;
0
◎
P11 group Protection parameters
P11.00
Phase-loss
protection
0x000–0x111
Ones:
0: Disable software input phase loss protection
1: Enable software input phase loss protection
Tens:
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds:
0: Disable hardware input phase loss protection
1: Enable hardware input phase loss protection
0x110
○
P11.01
Frequency-drop
at transient
power down
0: Disable
1: Enable
0
○