Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P26.45
Upper limit of
AO3 output
Setting range of P26.39: 0.00V–10.00V
Setting range of P26.40: P26.38–100.0%
Setting range of P26.41: 0.00V–10.00V
Setting range of P26.42: 0.000s–10.000s
Setting range of P26.43: -100.0%–P26.45
Setting range of P26.44: 0.00V–10.00V
Setting range of P26.45: P26.43–100.0%
Setting range of P26.46: 0.00V–10.00V
Setting range of P26.47: 0.000s–10.000s
100.0%
○
P26.46
Corresponding
AO3 output of
upper limit
10.00V
○
P26.47
AO3 output filter
time
0.000s
○
P26.48–
P26.52
Reserved
variables
0–65535
0
○
P28 group Master/slave control functions
P28.00
Master/slave
mode selection
0: The master/slave control is invalid
1: This machine is a master
2: This machine is a slave
0
◎
P28.01
Master/slave
communication
data selection
0: CAN
1: Reserved
0
◎
P28.02
Master/slave
control mode
Ones: Master/slave running mode selection
0: Master/slave mode 0
(The master and slave adopt speed control and
maintains the power balance by droop control)
1: Master/slave mode 1
(The master and slave must be in the same type of
vector control mode. The master is speed control,
and the slave will be forced to be in the torque
control mode.
2: Master/slave mode 2
Start in the slave first speed mode (master/slave
mode 0) and then switch to torque mode at a certain
frequency point (master/slave mode 1)
Tens: Slave start command source selection
0: Follow the master to start
1: Determined by P00.01
Hundreds: Slave transmitting/master receiving data
enable
0: Enable
1: Disable
0x001
◎