DRV-28 inverter
s Function parameter list
-133-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P01.17
Stop speed
detection time
0.00–100.00s
0.50s
◎
P01.18
Running
protection of
power-on
terminal
When the running command channel is controlled by
terminals, the system will detect running terminal
state automatically during power up.
0: Terminal running command is invalid during power
up. The inverter will not run during power up even if
the running command terminal is detected to be
valid, and the system is in running protection state.
The inverter will run only after this terminal is
cancelled and enabled again.
1: Terminal running command is valid during power
up. The system will start the inverter automatically
after initialization is done if the running command
terminal is detected to be valid during power up.
Note: This function must be set with caution,
otherwise, serious consequences may occur.
0
○
P01.19
Action selection
when the running
frequency is
below lower limit
(lower limit
should be larger
than 0)
This function code is used to set the running state of
inverter when the set frequency is below lower limit
frequency.
0: Run in lower limit of the frequency
1: Stop
2: Sleep
When the set frequency is below lower limit
frequency, the inverter coasts to stop; when the set
frequency is above lower limit again and continues to
be so after the time set by P01.20 elapses, the
inverter will be restored to running state
automatically.
0
◎
P01.20
Wake-up-from-sl
eep delay
This function code is used to set the sleep delay.
When the running frequency of inverter is below the
lower limit frequency, the inverter enters sleep state;
when the set frequency is above the lower limit again
and continues to be so after the time set by P01.20
elapses, the inverter will run automatically.
0.0s
○