DRV-28 inverter
s Function parameter list
-188-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
coefficient of
voltage regulator
during
overvoltage stall
of the bus voltage regulator during overvoltage stall.
Setting range: 0–1000
P11.23
Proportional
coefficient of
current regulator
during
overvoltage stall
This parameter is used to set the proportional
coefficient of the active current regulator during
overvoltage stall.
Setting range: 0–1000
60
○
P11.24
Integral
coefficient of
current regulator
during
overvoltage stall
This parameter is used to set the integral coefficient
of the active current regulator during overvoltage
stall.
Setting range: 0–2000
250
○
P11.25
Enable inverter
overload integral
0: Disabled
1: Enabled
When this parameter is set to 0, the overload timing
value is reset to zero after the inverter is stopped. In
this case, the determination of inverter overload
takes more time, and therefore the effective
protection over the inverter is weakened.
When this parameter is set to 1, the overload timing
value is not reset, and the overload timing value is
accumulative. In this case, the determination of
inverter overload takes less time, and therefore the
protection over the inverter can be performed more
quickly.
0
P11.26–
P11.27
Reserved
variables
0–65536
0
○
P12 group Parameters of motor 2
P12.00 Type of motor 2
0: Asynchronous motor
1: Synchronous motor
0
◎
P12.01
Rated power of
asynchronous
motor 2
0.1–3000.0kW
Depend
on model
◎
P12.02
Rated frequency
of asynchronous
motor 2
0.01Hz–P00.03 (Max. output frequency)
50.00Hz
◎