Frequency reference 1
Frequency reference 2
Frequency reference 3
CT1IL1, CT2IL1, VT1U1, VT2U1
CT1IL2, CT2IL2, VT1U2, VT2U2
CT1IL3, CT2IL3, VT1U3, VT2U3
Pick-up
Df/dt>/< pick-up setting
0.15…1.00 Hz/s, setting step 0.01 Hz
f> limit
10.00…70.00 Hz, setting step 0.01 Hz
f< limit
7.00…65.00 Hz, setting step 0.01 Hz
Pick-up inaccuracy
Df/dt
±5.0 %I
SET
or ±20 mHz/s
Frequency
±15 mHz (U > 30 V secondary)
±20 mHz (I > 30 % of rated secondary)
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio +/- 50 mHz)
±1.5 % or ±110 ms (max. step size: 100 mHz)
Start time and instant operation time (trip):
f
M
/f
SET
ratio +/- 20 mHz (overreach)
<180 ms
f
M
/f
SET
ratio +/- 200 mHz (overreach)
<90 ms
Reset
Reset ratio (frequency limit)
0.020 Hz
Instant reset time and start-up reset
- f
M
/f
SET
ratio +/- 50 mHz
<2 cycles or <60 ms (max. step size: 100 mHz)
No
Notte!
e!
• The frequency is measured two seconds after a signal is received.
9.2.1.15 Line thermal overload protection (TF>; 49F)
Table. 9.2.1.15 - 296. Technical data for the line thermal overload protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
TRMS phase currents (up to the 31
st
harmonic)
Settings
Time constants τ
1
Time constant value
0.0…500.00 min, step 0.1 min
Service factor (maximum overloading)
0.01…5.00 × I
N
, step 0.01 × I
N
Thermal model biasing
- Ambient temperature (Set –60.0…500.0 deg, step 0.1 deg and RTD)
- Negative sequence current
Thermal replica temperature estimates
Selectable between °C and °F
Outputs
- Alarm 1
- Alarm 2
- Thermal trip
- Trip delay
- Restart inhibit
0…150 %, step 1 %
0…150 %, step 1 %
0…150 %, step 1 %
0.000…3600.000 s, step 0.005 s
0…150 %, step 1 %
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04