Operating time characteristics
The operating timers’ behavior during a function can be set depending on the application. The same
pick-up signal starts both timers. When retrip is used the time grading should be set as follows: the
sum of specific times (i.e. the retrip time, the expected operating time, and the pick-up conditions'
release time) is shorter the set CBFP time. This way, when retripping another breaker coil clears the
fault, any unnecessary function triggers are avoided.
The following table presents the setting parameters for the function's operating time characteristics.
Table. 5.3.8 - 91. Setting parameters for operating time characteristics.
Name
Range
Step
Default
Description
Retrip
0: No
1: Yes
-
1: Yes
Retrip enabled or disabled. When the retrip is disabled, the output will not
be visible and the TRetr setting parameter will not be available.
Retrip
time
delay
0.000…1800.000s 0.005s 0.100s
Retrip start the timer. This setting defines how long the starting condition
has to last before a RETRIP signal is activated.
CBFP
0.000…1800.000s 0.005s 0.200s
CBFP starts the timer. This setting defines how long the starting condition
has to last before the CBFP signal is activated.
The following figures present some typical cases of the CBFP function.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
146
© Arcteq Relays Ltd
IM00013
Summary of Contents for AQ F205
Page 1: ...AQ F205 Feeder protection IED Instruction manual ...
Page 2: ......